Earth Resistance Clamp
Art.-No. 911-00051
| T2000
|
Copied
- Jaw Size 32 mm
- 99 Memory locations
- Resistance measurement on earth probes by means of ground loop method
- Direct measurement on earth probes without any cable breaking
- Measurement of leakage current on earth installations
- Setting of alarm thresholds on measurements
- Storage of measurement results
- Detection of current noise on measurements
- Data HOLD function
- Backlit
- Auto power off
Show more
Show less
More products in this product group:
| Application | Measuring earth ground rod resistance and leakage current in grounded systems without disconnecting the system |
| Content Accessories | Resistive test loop, Carry case |
| Description | Earth Resistance Clamp |
| PART DESCRIPTION | T2000 |
| Package Content packed in | box |
| Part No. | T2000 |
| Power Supply | 4x 1.5V AAA Batteries |
| Product Family | T2000 |
| Product Group | Earth Resistance Clamps |
| Type | T2000 |
| Height (H) | 66mm |
| Length (L) | 293mm |
| Width (W) | 90mm |
Feature
[AC Current (A)]
Parameter
[OA-80 mA, 80 - 65 mA, 650 - 999.5 mA, 1-3.995 mA, 4 - 20 mA]
Accuracy
[±2.5% + 1mA, ±2.5% + 20mA, ±2.5% + 0.003A, ±2.5% + 0.01A, ±2.5% + 0.05A]
Feature
[Resistance (Ω)]
Parameter
[0.01Ω - 0.999 Ω, 0.1Ω - 0.99 Ω, 1Ω - 49.9 Ω, 5Ω - 99.9 Ω, 100Ω - 199.9 Ω, 200Ω - 395 Ω, 400Ω - 590 Ω, 600Ω - 1000 Ω]
Accuracy
[±1.0% + 0.01Ω, ±1.0% + 0.01, ±1.5% + 0.1Ω, ±2.0% + 0.3Ω, ±3.0% + 1Ω, ±6.0% + 5Ω, ±10% + 10Ω, ±20% + 20Ω]
| Feature | Parameter | Accuracy |
|---|---|---|
|
AC Current (A) |
OA-80 mA 80 - 65 mA 650 - 999.5 mA 1-3.995 mA 4 - 20 mA |
±2.5% + 1mA ±2.5% + 20mA ±2.5% + 0.003A ±2.5% + 0.01A ±2.5% + 0.05A |
|
Resistance (Ω) |
0.01Ω - 0.999 Ω 0.1Ω - 0.99 Ω 1Ω - 49.9 Ω 5Ω - 99.9 Ω 100Ω - 199.9 Ω 200Ω - 395 Ω 400Ω - 590 Ω 600Ω - 1000 Ω |